Technical Data:
- Module Capacity (kWh) : 5,3
- Single Module Nominal Voltage (Vdc) : 52
- Application : Dual Voltage LV/HV
- Modules Expandibility:
- HV Mode : Max 16 Modules in Series with Single HV Box = One HV Cluster
Max 10 HV Clusters composed by maximum 16 modules in serial connection each
- LV Mode : Max 15 Modules in Parallel without WeHub = One LV Cluster
Max 7 LV Clusters composed by maximum 15 modules in parallel connection
- Cluster Net Capacity (with HV HUB) : Max 144 Modules per HV System
- Voltage Range (Vdc) : 47,5-58,4
- BMS dynamically adjust the operating values
- Cell Net Capacity (Ah) : 105
- Usable Capacity (Ah) : 100
- Dimension (mm) : 580 x 463 x 155
- Weight (kg) : 57,3
- Charge / Discharge Current (A) : 100 ( 150 30sec)
- Peak Discharge Current : 200 Peak 5 s
- Depth of Discharge : Up to 100%
- Communication Port : RS485, CAN, 232, Wi-Fi
- Modules in serial Connection : Up to 16 pcs ( 934Vdc Max String Voltage)
- Discharge Temperature : (°C) -20 ~ +60
- Charge Temperature : (°C) -10 ~ +55
- Shelf Temperature : (°C) -10 ~ +45
- Humidity (%) : 5 ~ 95
- Altitude (m) : < 3000
- Design life : 15 Years (25°c)
- Expected Life Cycles @ STC 80% DoD : > 8000 (25°C)
- Standards : IEC62619 UL1973 CE IEC 61000 UN38.3
- Features : Pre-Charge+Fuse LV+ Fuse HV+ Auto Contactor + Dual BMS+ Multi BMS FW management
- Applicable for Low Voltage and High Voltage systems, Four protection levels for HV Box, Real time balancing, Adaptive charge/discharge CAN logic, Three step adaptive charging logic, 2xDI/DO programmable ports, Mobile APP for monitoring, control, debugging, firmware update and historical information.
- Module net usable energy is managed by the BMS control logic to 100Ah
- 5K3 –XP Is designed to operate indoor or in Outdoor Cabinet approved by WeCo